14 AWG 12C Copper FR-XLPE CPE Jacket Control Cable 600V
Applications:
The 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial,aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operatingcontinuously at the conductor temperature not in excess of 90C for normal operation in wet and dry locations, 130C foremergency overload, and 250C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposedruns (TC-ER) per NEC 336.10
Also Known As:
14 AWG 12C 600V Control Cable, 14 AWG 12C FR-XLPE Insulated Control Cable, 16/2 CPE Jacketed Control Cable Flame-Retardant XLPE Control Cable, Industrial Control Cable XLPE/PVC Control Cable, Type TC-ER Cable, UL 1277 Cable, 600 Volt Instrumentation Cable.
Construction:
Conductor:
7 strands class B compressed bare copper per ASTM B3 and ASTM B8
Insulation:
Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
Filler:
Polypropylene filler on cables with 5 or less conductors
Binder:
Polyester flat thread binder tape applied for cables with more than 5 conductor
Rip Chord:
Rip chord for ease of jacket removal
Overall Jacket:
Chlorinated Polyethylene (CPE) Jacket
Standards:
ASTM B3 Standard Specification for Soft or Annealed Copper Wire
ASTM B8 Concentric-Lay-Stranded Copper Conductors
UL 1277 Electrical Power and Control Tray Cables
UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 – (210,000 Btu/hr)
VW-1 (Vertical-Wire) Flame Test
Specification:
Size: 14 AWG
Number of Conductors: 12
Diameter OverConductor(inch): 0.070
InsulationThickness (Mil): 30
Jacket Thickness (Mil): 60
Approx. OD (In): 0.659
Copper Weight (Lbs/1000’Ft): 154
Approx. Weight (Lbs/1000’Ft): 303
DC Resistance /1000ft: 2.630
AC Resistance @ 90C /1000ft: 3.288
MinBendingRadius (In): 2.6
Allowable Ampacity At 60C: 9
Allowable Ampacity 75C: 11
Allowable Ampacity 90C: 12
|