12 AWG 3C Multi-Conductor FR-XLPE LSZH Jacket Control Cable CU 600V
Applications:
The 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial,aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operatingcontinuously at the conductor temperature not in excess of 90C for normal operation in wet and dry locations, 130C foremergency overload, and 250C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposedruns (TC-ER) per NEC 336.10.
Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation SOLONON Low Smoke Zero Halogen (LSZH) Jacket, Control Cable Conductor Identification Method 1 Table 2. Silicone Free
Also Known As:
12 AWG 3C 600V control cable, FR-XLPE insulated cable, LSZH jacket cable, copper control cable, multi-conductor cable, 12 AWG 3C low smoke zero halogen cable, 12 AWG 3C flame retardant cable, tray-rated control cable, 12 AWG 3C industrial control wire, UL 1277 control cable.
Standards:
ASTM B3 Standard Specification for Soft or Annealed Copper Wire
ASTM B8 Concentric-Lay-Stranded Copper Conductors
UL 44 Thermoset-Insulated Wires and Cables
UL 1277 Electrical Power and Control Tray Cables
UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 – (210,000 Btu/hr)
VW-1 (Vertical-Wire) Flame Test
Construction:
Conductor:
7 strands class B compressed bare copper per ASTM B3 and ASTM B8
Insulation:
Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
Filler:
Polypropylene filler on cables with 5 or less conductors
Binder:
Polyester flat thread binder tape applied for cables with more than 5 conductors
Rip Chord:
Rip chord for ease of jacket removal
Overall Jacket:
SOLONON Low Smoke Zero Halogen (LSZH) Jacket
Specifications:
Size: 12 AWG
Number of Conductors: 3
Diameter OverConductor(inch): 0.087
InsulationThickness (Mil):30
Jacket Thickness (Mil): 45
Approx. OD (In): 0.408
Copper Weight (Lbs/1000’Ft): 61
Approx. Weight (Lbs/1000’Ft): 118
MinBendingRadius (In): 1.6
Allowable Ampacity At 60C (Amp): 20
Allowable Ampacity At 75C (Amp): 20
Allowable Ampacity 90C (Amp): 20