1/3C + 18/9C 6 AWG Ground Type TC/TC-ER-JP Aluminum Generator Cable Black
Applications:
A multi-conductor all-in-one cable for connecting a 17kW 24kW generator to a transfer switch. A multi-conductorall-in-one cable for connecting a generator to a transfer switch. JP (Joist Pull) rated per the 2017 NEC 336.10(9). Black jacket and color-coded inner conductors.
Also Known As:
Generator Cable, Type TC/TC-ER-JP, Multi-Conductor Generator Cable, PVC Generator Cable, Type TC Cable, Type TC-ER Wire, Generator Wire, joist Pull Generator Cable, Aluminum Generator Cable, 17kW Generator Cable, 24kW Generator Cable, 1/3C + 18/9C 6 W/G Cable, Black Generator Cable.
Construction:
Conductors:
Element 1: Aluminum 8000 series
Element 2: Annealed bare Aluminum Class K
Element 3: Aluminum 8000 series
Insulation:
Element 1, 2 & 3: Polyvinylchloride (PVC) & Nylon
Jacket:
Sunlight resistant and direct burial approved PVC with ripcord rated 90C wet or dry per UL 1277
Assembly:
All 3 Elements or Conductors are cabled together with Non-Hygroscopic Polypropylene fillers as required for a circular cross-section with a clear mylar binder tape and jacketed.
Color Code:
Element 1: Black, White, Red
Element 2: Black, Red, Yellow, Yellow/Black, Blue, White,White/Blue, Purple, Purple/Black
Element 3: Green Ground
Standards:
UL Listed as TC-ER-JP per UL Standard 1277
Rated 90C wet or dry to meet UL 83 for THHN/THWN
Meets cold bend test at -40C
ICEA S-73-532. ICEA S-95-658, where applicable
Meets UL 1581 & 1202 (FT-4) 70,000 BTU/HR & ICEA T-29-520 210,000 BTU/HR requirements
REACH compliant per Regulation (EC) No 1907/2006 (233)Updated January 17, 2023
Cable is suitable for use in Class I Division 2 hazardouslocations
Element 1 & 2 conductors pass UL VW-1 flame test, ratedTHWN/VW-1
ASTM B3, B8, B174, B787
UL approved for Direct Burial & Sunlight Resistant
Applications
Specification:
Size: 1 AWG (3 Conductors), 18 AWG (9 Conductors)
Ground Wire Size:6 AWG
Jacket:Polyvinylchloride (PVC) & Nylon
Jacket Color:Black
Outside Diameter: 1.086 inches
Weight lbs/kft:675 lbs
Allowable Ampacity:100 Amps
***THIS MATERIAL IS NON-RETURNABLE***
All values are nominal and subject to correction.
*Ampacity according to NEC 310.15(B)(16) @30C THWN 75C insulated wires.
**Installations shall follow NEC, applicable correcting factors shall be considered when conditions vary.