Description
[pdf] [/pdf]
500 MCM Type MV-90 2.4KV EPR/CPE Unshielded Power Cable
Applications:
For use in caustic environments in power circuits up to 2.4kV when installed in open air, conduit, duct, cable tray when CT rated, in wet and dry locations. Used for applications in chemical plants, refineries, steel mills, industrial plants, commercial buildings, utility substations and generating stations.
Also Know As:
500 MCM Medium voltage power cables, 500 MCM Power cable, 500 MCM MV90 Cables, 500 MCM EPR Power cable, 500 MCM CPE Jacketed Cables, 500 MCM Medium Voltage Cables, 500 MCM 90C MV Cables.
Conductor:Compressed, soft bare annealed copper per ASTM B-3,Class B stranding per ASTM B-8, with a semi-conductingconductor shield
Insulation: Ethylene propylene rubber (EPR) per ICEA standards
Jacket: XL-CPE per ICEA standards
Flame Tests: UL and IEEE (70,000 BTU/hr) Flame Test for CT-listedsizes 1/0 AWG and larger
Strandads:
ICEA S-96-659
UL Standard 1072
NEMA WC71
CT rating must be requested, CT ratings are available on sizes 1/0 AWG and larger.
PVC jacket available upon request
Specification:
Size: 500 MCM
No of Strands: 37
Insulation Thickness: 140 Mils
Jacket thickness: 110 Mils
Overall Diameter: 1.37 Inches
Weight Lbs/Mft: 2130
Catalog Number: HW201 50001






Reviews
There are no reviews yet.