| Conduit Size | 1 Inch |
| Diameter Over Inner Jacket | 1.041 Inch |
| Approximate Outside Diameter (OD) | 1.290 Inch |
| Minimum Bend Radius | 13.0 Inch |
| Color | Gray |
Construction :
Armor :
Titan2 Type UL is manufactured using a spiral-wound strip of heavy-gauge, corrosion-resistant, hot-dipped galvanized steel. For trade sizes 3/8″ through 1-1/4″, the core features a square-locked steel strip with an integral copper bonding strip enclosed within the steel convolutions.
Jacket :
A rugged, flame-retardant gray PVC jacket is extruded over the steel core. This jacket provides protection against liquids, oils, certain chemicals, temperature variations, extreme weather, and sunlight.
Features :
Provides a protective thermoplastic conduit/raceway designed to seal out water, liquids, abrasives, alcohol, coolants, corrosive fumes and gases, dirt, grease, mineral acids, non-concentrated fixed alkalines, petroleum oils, salt air and spray, and weather.
Smooth interior for easy and efficient wire pulling.
UV- and sunlight-resistant outer jacket.
Temperature rating: -30C to 80C, 60C Oil (-22F to 176F; 140F Oil).
Compatible with standard liquid-tight fittings used for LFNC-B applications.
Suitable for direct burial, including concrete encasement.